Please file in Service Binder
VITOTRONIC
r
200
VITOTRONIC
r
300-K
Vitotronic 200, Type HO1B
Digital boiler control unit
Vitotronic 300-K, Type MW2B
Weather-compensated, digital cascade control unit
for use by heating contractor
Installation and Service
Instructions
5693 976 - 04 02/2015
Vitotronic 300-K
Vitotronic 200
Product may not be exactly as shown
Read and save these instructions
for future reference.
IMPORTANT
Certified as a component
part for Viessmann boilers
Zobrazit stránku 0
1 2 3 4 5 6 ... 95 96

Shrnutí obsahu

Strany 1 - IMPORTANT

Please file in Service BinderVITOTRONIC r 200VITOTRONIC r 300-KVitotronic 200, Type HO1B Digital boiler control unitVitotronic 300-K, Type MW2B Weathe

Strany 2 - Product Information

Vitotronic 200 and 300-K Installation and Service5693 976 - 0410Installation SequencePreparing Boilers for Cascade Mode (continued)Installation of the

Strany 3 - Table of Contents

115693 976 - 04Vitotronic 200 and 300-K Installation and ServiceInstallation SequenceClosing the control unit cover1. Install the cover onto the cont

Strany 4

Vitotronic 200 and 300-K Installation and Service5693 976 - 0412IMPORTANTPreparing Boilers for Cascade Mode (continued)Installation SequenceThe follow

Strany 5 - About these Instructions

135693 976 - 04Vitotronic 200 and 300-K Installation and ServiceInstallation SequenceOverview of Electrical Connections, Vitotronic 300-KElectrical co

Strany 6 - For your Safety

Vitotronic 200 and 300-K Installation and Service5693 976 - 0414Installation SequenceOverview of Electrical Connections, Vitotronic 300-K (continued)L

Strany 7 - System Example

155693 976 - 04Vitotronic 200 and 300-K Installation and ServiceInstallation SequenceMounting the Control Unit1. Fasten metal backplate onto mounting

Strany 8 - System Example (continued)

Vitotronic 200 and 300-K Installation and Service5693 976 - 0416Installation SequenceLegendA Cables with moulded strain reliefB On-site cables; strip

Strany 9

175693 976 - 04Vitotronic 200 and 300-K Installation and ServiceInstallation SequenceConnecting PumpsPumps 120VRated current: 2 A~* Maximum pump out

Strany 10 - Installation Sequence

Vitotronic 200 and 300-K Installation and Service5693 976 - 0418Installation Sequence 120V External Connection120V pumps with an amperage draw of >

Strany 11

195693 976 - 04Vitotronic 200 and 300-K Installation and ServiceInstallation SequenceConnecting ActuatorsAvailable connectionsgS A1 Motor for 3-way mi

Strany 12

Vitotronic 200 and 300-K Installation and Service5693 976 - 042GeneralSafety, Installation and Warranty RequirementsPlease ensure that these instructi

Strany 13

Vitotronic 200 and 300-K Installation and Service5693 976 - 0420Installation SequenceConnecting the Central Fault Message Facility Rated voltage

Strany 14

215693 976 - 04Vitotronic 200 and 300-K Installation and ServiceInstallation SequenceExternal Demand via 0–10V InputDemand for a system supply tempera

Strany 15 - Mounting the Control Unit

Vitotronic 200 and 300-K Installation and Service5693 976 - 0422The mixing valves are opened A or closed B when the contact is closed.Note: ‘Live’ co

Strany 16 - Connecting Sensors

235693 976 - 04Vitotronic 200 and 300-K Installation and ServicePreselected heating program (Contact open) Coding Changed heating program (Contact clo

Strany 17 - Connecting Pumps

Vitotronic 200 and 300-K Installation and Service5693 976 - 0424Installation SequenceMaking the LON Connection (continued)LegendA Control unit or Vito

Strany 18 - 120V External Connection

255693 976 - 04Vitotronic 200 and 300-K Installation and ServiceInstallation SequencePower SupplyWARNINGThe control must be grounded.Ensure that “L”,

Strany 19 - Connecting Actuators

Vitotronic 200 and 300-K Installation and Service5693 976 - 0426Installation Sequence Fitting the Front Part of the Control UnitNote: Route the ribbo

Strany 20

275693 976 - 04Vitotronic 200 and 300-K Installation and ServiceCommissioningChanging the LanguageThe cascade communication module must be fitted into

Strany 21

Vitotronic 200 and 300-K Installation and Service5693 976 - 0428CommissioningConfiguring a Multi Boiler System (continued)ABCDEBoiler number 1Code “07

Strany 22

295693 976 - 04Vitotronic 200 and 300-K Installation and ServiceCommissioningConnecting the Control Unit to the LON System H See also chapter “Configu

Strany 23 - Making the LON Connection

35693 976 - 04Vitotronic 200 and 300-K Installation and ServiceTable of Contents PageGeneralSafetyPreparing for InstallationInstallation SequencesComm

Strany 24

Vitotronic 200 and 300-K Installation and Service5693 976 - 0430CommissioningIn code 1, set the following coding addresses:“00” System scheme“35” Numb

Strany 25 - Power Supply

315693 976 - 04Vitotronic 200 and 300-K Installation and ServiceCommissioningChecking Outputs Actuators and SensorsTesting the relay – Vitotronic 300-

Strany 26 - Opening the Control Unit

Vitotronic 200 and 300-K Installation and Service5693 976 - 0432Checking sensors – Vitotronic 300-K1. Press OK and simultaneously for approx. 4 sec.

Strany 27 - Set Time and Date

335693 976 - 04Vitotronic 200 and 300-K Installation and ServiceCommissioningChecking Outputs on Actuators and Sensors (continued)Standard room temper

Strany 28 - Commissioning

Vitotronic 200 and 300-K Installation and Service5693 976 - 0434Calling up Coding Level 1 – Vitotronic 200For the Vitotronic 200, see boiler Service I

Strany 29

355693 976 - 04Vitotronic 200 and 300-K Installation and ServiceCodingCoding in the factory setting Possible changeSystem design (boiler connected to

Strany 30

Vitotronic 200 and 300-K Installation and Service5693 976 - 0436Coding 1 Vitotronic 300-K1. Press OK and simultaneously for approx. 4 sec.2. “Codin

Strany 31

375693 976 - 04Vitotronic 200 and 300-K Installation and ServiceCoding 1 Vitotronic 300-K“General” GroupCodingCoding in the factory set condition Poss

Strany 32

Vitotronic 200 and 300-K Installation and Service5693 976 - 0438“Cascade” Group CodingCoding in the factory set condition Possible changeNumber of boi

Strany 33

395693 976 - 04Vitotronic 200 and 300-K Installation and Service“Solar” GroupCodingCoding in the factory set condition Possible changeSpeed control so

Strany 34 - Coding 1 Vitotronic 200

Table of Contents4 Page5693 976 - 03Vitotronic 200 and 300-K Installation and ServiceCoding 1 Vitotronic 200Coding 1 Vitotronic 300-KCoding 2 Vitotron

Strany 35 - “Boiler” Group

Vitotronic 200 and 300-K Installation and Service5693 976 - 0440“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” GroupParameter address A5:..

Strany 36 - Coding 1 Vitotronic 300-K

415693 976 - 04Vitotronic 200 and 300-K Installation and Service“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group (continued)Coding in t

Strany 37

Vitotronic 200 and 300-K Installation and Service5693 976 - 0442“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group (continued)Coding in t

Strany 38 - “DHW” Group

435693 976 - 04Vitotronic 200 and 300-K Installation and Service“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group (continued)Coding in t

Strany 39 - “Solar” Group

Vitotronic 200 and 300-K Installation and Service5693 976 - 0444Coding 2 Vitotronic 200Calling up Coding Level 2 – Vitotronic 200Note: At coding level

Strany 40

455693 976 - 04Vitotronic 200 and 300-K Installation and ServiceCoding 2 Vitotronic 200“General” GroupCodingCoding in the factory setting Possible cha

Strany 41

Vitotronic 200 and 300-K Installation and Service5693 976 - 0446CodingCoding in the factory setting Possible change3B:0 Function input DE2 at extensio

Strany 42

475693 976 - 04Vitotronic 200 and 300-K Installation and Service“General” GroupCodingCoding in the factory setting Possible change53:1Function connect

Strany 43

Vitotronic 200 and 300-K Installation and Service5693 976 - 0448Coding 2 Vitotronic 200CodingCoding in the factory setting Possible change01:2 Do not

Strany 44 - Coding 2 Vitotronic 200

495693 976 - 04Vitotronic 200 and 300-K Installation and ServiceCalling up Coding Level 2 – Vitotronic 300-KNote: H In coding level 2, all codes are a

Strany 45

55693 976 - 04Vitotronic 200 and 300-K Installation and ServiceSafetyTake note of all symbols and notations intended to draw attention to potential ha

Strany 46

Vitotronic 200 and 300-K Installation and Service5693 976 - 0450“General” GroupValue address 00: ...System version Description2 1 One heating circuit

Strany 47

515693 976 - 04Vitotronic 200 and 300-K Installation and Service“General” Group (continued)Coding in the factory set condition Possible change50:10 St

Strany 48

Vitotronic 200 and 300-K Installation and Service5693 976 - 0452“General” Group (continued)Coding in the factory set condition Possible change76:0 Wit

Strany 49 - Coding 2 Vitotronic 300-K

535693 976 - 04Vitotronic 200 and 300-K Installation and Service“General” Group (continued)Coding in the factory set condition Possible change82:3 Sum

Strany 50

Vitotronic 200 and 300-K Installation and Service5693 976 - 0454“General” Group (continued)Coding in the factory set condition Possible change99:0Conn

Strany 51 - “General” Group (continued)

555693 976 - 04Vitotronic 200 and 300-K Installation and Service“Cascade” GroupCodingCoding in the factory set condition Possible change35:4 4 boilers

Strany 52

Vitotronic 200 and 300-K Installation and Service5693 976 - 0456“Cascade” Group (continued)Coding in the factory set condition Possible change42:31 No

Strany 53

575693 976 - 04Vitotronic 200 and 300-K Installation and Service“DHW” Group CodingCoding in the factory set condition Possible change55:0 DHW tank hea

Strany 54

Vitotronic 200 and 300-K Installation and Service5693 976 - 0458“DHW” Group (continued)Coding in the factory set condition Possible change67:40 With t

Strany 55

595693 976 - 04Vitotronic 200 and 300-K Installation and Service“Solar” GroupOnly in conjunction with solar control module, type SM1.CodingCoding in t

Strany 56 - “Cascade” Group (continued)

Vitotronic 200 and 300-K Installation and Service5693 976 - 046If you smell gasH Don’t smoke! Don’t use naked flames or cause sparks (e.g. by swit

Strany 57

Vitotronic 200 and 300-K Installation and Service5693 976 - 0460“Solar” Group (continued)Coding in the factory set condition Possible change0E:1 Calcu

Strany 58 - “DHW” Group (continued)

615693 976 - 04Vitotronic 200 and 300-K Installation and Service“Solar” Group (continued)Coding in the factory set condition Possible change24:40 Star

Strany 59

Vitotronic 200 and 300-K Installation and Service5693 976 - 0462“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” GroupCodingCoding in the fac

Strany 60 - “Solar” Group (continued)

635693 976 - 04Vitotronic 200 and 300-K Installation and Service“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group (continued)Coding in t

Strany 61

Vitotronic 200 and 300-K Installation and Service5693 976 - 0464“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group (continued)Coding in t

Strany 62

655693 976 - 04Vitotronic 200 and 300-K Installation and Service“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group (continued)Coding in t

Strany 63

Vitotronic 200 and 300-K Installation and Service5693 976 - 0466“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group (continued)Coding in t

Strany 64

675693 976 - 04Vitotronic 200 and 300-K Installation and ServiceService ScansCalling up the Service LevelVitotronic 2001. Press OK and simultaneous

Strany 65

Vitotronic 200 and 300-K Installation and Service5693 976 - 0468Service ScansScanning Operating Data H Vitotronic 300-K:

Strany 66

695693 976 - 04Vitotronic 200 and 300-K Installation and ServiceService ScansBrief Scan Vitotronic 200In the brief scan, you can scan temperatures, so

Strany 67 - Calling up the Service Level

75693 976 - 04Vitotronic 200 and 300-K Installation and ServicePreparing for InstallationSystem ExampleMulti boiler system with several heating circui

Strany 68 - Scanning Operating Data

Vitotronic 200 and 300-K Installation and Service5693 976 - 0470In the brief scan, you can scan temperatures, software versions and connected componen

Strany 69 - Brief Scan Vitotronic 200

715693 976 - 04Vitotronic 200 and 300-K Installation and ServiceTroubleshootingFault Display Vitotronic 200Calling up acknowledged fault messagesExten

Strany 70 - Brief Scan Vitotronic 300-K

Vitotronic 200 and 300-K Installation and Service5693 976 - 0472TroubleshootingFault Display Vitotronic 300-K (continued)Fault codesDisplayed fault co

Strany 71 - Fault Display Vitotronic 200

735693 976 - 04Vitotronic 200 and 300-K Installation and ServiceTroubleshootingFault Display Vitotronic 300-K (continued)Fault codesDisplayed fault co

Strany 72 - Troubleshooting

Vitotronic 200 and 300-K Installation and Service5693 976 - 0474TroubleshootingFault Display Vitotronic 300-K (continued)Fault codesDisplayed fault co

Strany 73

755693 976 - 04Vitotronic 200 and 300-K Installation and ServiceTroubleshootingFault Display Vitotronic 300-K (continued)Fault codesDisplayed fault co

Strany 74

Vitotronic 200 and 300-K Installation and Service5693 976 - 0476TroubleshootingFault Display Vitotronic 300-K (continued)Fault codesDisplayed fault co

Strany 75

775693 976 - 04Vitotronic 200 and 300-K Installation and ServiceTroubleshootingFault Display Vitotronic 300-K (continued)Fault codesDisplayed fault co

Strany 76

Vitotronic 200 and 300-K Installation and Service5693 976 - 0478Function Description, Vitotronic 200Boiler Water Temperature ControlBrief description

Strany 77

795693 976 - 04Vitotronic 200 and 300-K Installation and ServiceFunction Description, Vitotronic 300-KCascade Control Control sequenceStand-alone cont

Strany 78 - 5693 976 - 04

Vitotronic 200 and 300-K Installation and Service5693 976 - 048Preparing for InstallationSystem Example (continued)Vitotronic 200 (set codes at every

Strany 79 - Cascade Control

Vitotronic 200 and 300-K Installation and Service5693 976 - 0480Condensing strategy H It is the aim of the condensing strategy to operate as many

Strany 80 - Cascade Control (continued)

815693 976 - 04Vitotronic 200 and 300-K Installation and ServiceFunction Description, Vitotronic 300-KCascade Control (continued)Rated output inTotal

Strany 81

Vitotronic 200 and 300-K Installation and Service5693 976 - 0482Brief description H The control unit comprises control circuits for one heating circui

Strany 82 - Heating Circuit Control

835693 976 - 04Vitotronic 200 and 300-K Installation and ServiceFunction Description, Vitotronic 300-KHeating Circuit Control (continued)System dynami

Strany 83 - Set room temperature

Vitotronic 200 and 300-K Installation and Service5693 976 - 0484Function Description, Vitotronic 300-KHeating Circuit Control (continued)Raising the r

Strany 84

855693 976 - 04Vitotronic 200 and 300-K Installation and ServiceFunction Description, Vitotronic 300-KDHW Tank Temperature ControlIn conjunction with

Strany 85 - DHW Tank Temperature Control

Vitotronic 200 and 300-K Installation and Service5693 976 - 0486Function Description, Vitotronic 300-KDHW Tank Temperature Control (continued)Control

Strany 86

875693 976 - 04Vitotronic 200 and 300-K Installation and ServiceDesignsConnection and Wiring DiagramsOverviewLegendA1 Extension PCB heating circuits

Strany 87

Vitotronic 200 and 300-K Installation and Service5693 976 - 0488DesignsConnection and Wiring Diagrams (continued)Main PCB LVLegend! Outside temperat

Strany 88

895693 976 - 04Vitotronic 200 and 300-K Installation and ServiceDesignsConnection and Wiring Diagrams (continued)Main PCB 120V~LegendsÖ Heating circ

Strany 89

95693 976 - 04Vitotronic 200 and 300-K Installation and ServiceInstallation SequencePreparing Boilers for Cascade ModeOpening the control unit coverFo

Strany 90 - Components

Vitotronic 200 and 300-K Installation and Service5693 976 - 0490ComponentsSensorsNote: H The supply temperature sensor can be used as a con

Strany 91

915693 976 - 04Vitotronic 200 and 300-K Installation and ServiceComponentsExtension for Heating Circuits 2 and 3 (accessory)For connecting two extensi

Strany 92 - Mixing Valve Motor Kit

Vitotronic 200 and 300-K Installation and Service5693 976 - 0492ComponentsMixing Valve Motor KitComponents: H Mixing valve motor (not for flanged mixi

Strany 93

5693 976 - 04Vitotronic 200 and 300-K Installation and Service93Components Extension EA1 Accessory (optional)The DHW recirculation pump is started by

Strany 94 - Parts List

Vitotronic 200 and 300-K Installation and Service5693 976 - 0494Parts ListsParts ListWhen ordering spare parts:Quote the part and serial no. (see type

Strany 95 - Specification

955693 976 - 04Vitotronic 200 and 300-K Installation and ServiceSpecificationFor the Vitotronic 200, see boiler Service InstructionsRated voltage

Strany 96

Vitotronic 200 and 300-K Installation and Service5693 976 - 04 Technical information subject to change without notice. Printed on